Level solutions

 

Sensemaster supply Vega products to solve level sensing and level monitoring applications in tanks and silos.

Vega products are suitable for measuring level in the Water and Waste, Food and Beverage, Chemical and Petrochemical and Quarry Process Industries.

 Level control technologies include the following

 

 Radar sensors

This includes the VEGAPULS 62, the universal genius for level measurement of liquids under difficult conditions

  • Measuring range - Distance   35 m.
  • Process temperature   -196 ... 450 °C
  • Process pressure   -1 ... 160 bar
  • Accuracy   ± 2 mm
 

 Ultrasonic sensors

This includes the VEGASON 62, an ultrasonic sensor for continuous level measurement of liquids and bulk solids.

  • Measuring range - Distance   8 m
  • Process temperature   -40 ... 80 °C
  • Process pressure   -0,2 ... 2 bar
  • Accuracy   ± 10 mm
 

 Guided microwave sensors

This includes the VEGAFLEX 86. The VEGAFLEX 86 level sensor measures maintenance-free all liquids under extreme pressure and temperature conditions.

  • Measuring range - Distance   75 m
  • Process temperature   -196 ... 450 °C
  • Process pressure   -1 ... 400 bar
  • Accuracy   ± 2 mm
 

 Capacitive sensors

This includes the VEGACAL 62, designed for level measurement of bulk solids and can also be used in non-conductive liquids such as e.g. oil.

  • Measuring range - Distance   6 m
  • Process temperature   -50 ... 200 °C
  • Process pressure   -1 ... 64 bar
 Capacitive

 

 Vibration sensors

This includes the VEGASWING 61. It is a universal level switch for use in all liquids. It detects reliably with millimetre accuracy the limit level. The instrument can be used as empty or full detector

  • Process temperature   -50 ... 250 °C
  • Process pressure   -1 ... 64 bar
 

 

 Process pressure sensor

This includes VEGABAR 82. The VEGABAR 82 pressure transmitter can be used universally for the measurement of gases, vapours and liquids.

  • Measuring range - Pressure   -1 ... 100 bar
  • Process temperature   -40 ... 150 °C
  • Process pressure   -1 ... 100 bar
  • Accuracy   0,05 %
 

 Hydrostatic sensors

This includes the VEGABAR 86, a submersible pressure transmitter for level measurement in wells, basins and open vessels.

  • Measuring range - Distance   250 m
  • Measuring range - Pressure   0 ... 25 bar
  • Process temperature   -20 ... 100 °C
  • Process pressure   0 ... 25 bar
  • Accuracy   0,1 %
 

 Differential pressure sensors

This includes the VEGADIF 65. It can be used universally for the measurement of liquids, gases and vapours. Typical applications are level measurements in pressurized vessels as well as flow measurements in combination with DP flow elements.

  • Measuring range - Pressure   1 ... 40 bar
  • Process temperature   -40 ... 400 °C
  • Process pressure   -1 ... 420 bar